Hot water storage sizing

Storage volume and reheat time, sized together from a 24-hour draw-off profile and the heating duty you have: essential for heat pumps, where a slower reheat needs more volume. Not from counting outlets. Commercial buildings are sized on their peak hour from published demand figures.

The building

The tapping profile below decides the answer, not these counts. The outlets go with your result for our check and help you pick the profile: compare them with what each profile contains, further down.

Heat source and store
More assumptions you can change

Indicative result

Storage volume and reheat time

Required storage volume
58 litres
at 55 °C: 52 L usable ÷ 90%
Reheat time
37 min
58 L from 10 °C to 55 °C at 5 kW, less standing loss
Usable energy the store must hold
2.7 kWh (52 L usable)
Store at its lowest
08:16
Day's hot water energy from the store
11.65 kWh + 1.14 kWh standing loss
Recovery of the largest deficit
33 min

Method: energy-balance method per EN 12831-3 (via EU 814/2013 tapping profiles). The tapping profiles are Commission Regulation (EU) No 814/2013, Annex III, Table 1 "Load profiles of water heaters" (legislation.gov.uk), the profiles World Heat’s ErP ratings are declared against. This tool follows the standard’s approach; it is not the standard.

Indicative only. This result must be confirmed with World Heat before specification. Send it to our technical sales team with the form below, or email sales@whcylinders.co.uk (your inputs and result are filled in), or call 0161 343 8610.

Stored below 60 °C. HSE guidance (HSG274 Part 2) is to store hot water at 60 °C or above, so a store held at 55 °C needs a thermal disinfection (pasteurisation) regime, e.g. a timed cycle to 60 °C or above by the heat source or an immersion heater. Raising 58 L from 55 °C to 60 °C takes about 0.34 kWh, 4 min at 5 kW. That energy isn’t in the daily balance above.

Matching World Heat cylinders

The smallest standard heat pump cylinder in each range that holds at least 58 litres.

  • Climacyl · Standard

    90 litres

    90CLIMACYLSS2

    Declared standing loss 1.14 kWh/24h

    View the range
  • Ecoslim · Standard

    90 litres

    90ECOSLIMSS2

    Declared standing loss 1.05 kWh/24h

    View the range
  • Climabuff · Slim

    120 litres

    120CLIMABUFFSLIM

    Declared standing loss 1.33 kWh/24h

    View the range

Duty against volume

The same profile and assumptions at other duties. Less duty, more volume and a longer reheat.

Duty against volume
DutyStorage volumeReheat time
68 L1 h 27 min
62 L49 min
5 kW (yours)58 L37 min
48 L20 min
39 L12 min
22 L5 min
24-hour energy balance (kWh, cumulative from 00:00)
  • Stored at 00:00 + heat supplied
  • Hot water demand + standing loss
Cumulative demand reaches 12.79 kWh over the day. The store is at its lowest at 08:16, which sets the usable energy the store must hold: 2.7 kWh.0510152000:0006:0012:0018:0000:00Store lowest 08:16

Usable energy in the store (kWh)

02.5500:0006:0012:0018:0000:00
Show the balance as a table (hourly)
Hot water balance, hour by hour
TimeDemand + loss (cumulative, kWh)Stored at 00:00 + supplied (kWh)In store (kWh)
01:000.052.742.7
02:000.092.792.7
03:000.142.842.7
04:000.192.892.7
05:000.242.932.7
06:000.292.982.7
07:000.333.032.7
08:002.14.792.7
09:006.068.762.7
10:006.329.022.7
11:006.479.172.7
12:006.739.432.7
13:007.099.792.7
14:007.149.842.7
15:007.299.992.7
16:007.4410.142.7
17:007.610.292.7
18:007.6410.342.7
19:008.0110.72.7
20:008.1610.862.7
21:008.9411.642.7
22:0012.715.42.7
23:0012.7515.442.7
00:0012.7915.492.7

Assumptions used

Method
energy-balance method per EN 12831-3 (via EU 814/2013 tapping profiles). An implementation of the EN 12831-3 approach, not the standard itself.
Tapping profile
L: 24 draw-offs from 07:00, 11.655 kWh a day (Qref), from Commission Regulation (EU) No 814/2013, Annex III, Table 1 "Load profiles of water heaters".
Profile energy base
The profiles' energies are counted from a 10 °C cold feed (Annex I (7); Tm = 10 °C for bath and dishwashing draw-offs).
Mixed to stored water
Each draw-off is delivered at its peak temperature Tp where the table gives one, else its useful temperature Tm. Its litres at that temperature are worked out from the profile energy, then re-based to your 10 °C cold feed and converted to stored water at 55 °C.
Water
Specific heat 4.186 kJ/(kg·K), 1 kg per litre.
Heat source
5 kW available to the store, whenever needed (24 hours), putting back what has been drawn up to that duty.
Standing loss
1.14 kWh/24h, the declared standing loss of 90CLIMACYLSS2 (90 L), the smallest matching World Heat cylinder; the declared figure is used as it is, not adjusted to the storage temperature. Spread evenly over the day.
Usable volume
90% of the stored volume can be drawn off hot enough (mixing and stratification allowance). Adjust for the cylinder.
Time step
One minute. Each draw-off is spread evenly over its duration at the profile's flow rate. Days are repeated until the pattern settles, so the store starts the day as the previous day left it.
Outlets
Recorded for World Heat's check. The method sizes from the 24-hour profile, not from counting outlets (no loading units).
Not included
Limits on the duty the cylinder's coil can take, secondary circulation and pipework losses, energy for thermal disinfection, draw-offs beyond the profile (e.g. several showers at once), and diversity across several dwellings.

What each profile contains

Counted from Commission Regulation (EU) No 814/2013, Annex III, Table 1 "Load profiles of water heaters". Your outlets: 1 shower, 1 bath, 2 basins and sinks. Shower-sized: 40 °C at 6 l/min or more. Bath fill: to 40 °C at 10 l/min or more.

What each profile contains
ProfilekWh/day≈ L at 40 °CShower-sizedBath fillsTo 55 °COtherPeak flow
0.34510000232 l/min
2.160000202 l/min
2.16000033 l/min
2.16000295 l/min
5.845168202196 l/min
L11.6553341221910 l/min
19.075471322410 l/min
24.537031322416 l/min

Ask World Heat to confirm this

Your inputs, the result and every assumption above go with your message to sales@whcylinders.co.uk. Add how to reach you.

Email or phone * — one is enough.

We’ll only use your details to respond to your enquiry. Privacy policy

Use my own email

The ranges this tool recommends from: Unvented cylinders, Heat pump cylinders and Storage Calorifiers/Cylinders.

Rather talk it through? Our technical sales team sizes cylinders every day: 0161 343 8610. See all our design tools.

CallRequest a quote Request a quote Request a quote